Ohm and The Breaker in the cold garage
Ohm & The Breaker — a 17-year-old electrical apprentice on her first service call
A customer's garage breaker keeps tripping. On one 15 A circuit wired with 14-gauge copper, there is an 1,800 W heater and a 600 W kettle.
Ohm: power is volts × amps, so current = watts ÷ volts. 1,800 W + 600 W is 2,400 W; at 120 V that is 20 A. The heater alone is 15 A.
The Breaker: 14-gauge copper is protected at 15 A. The breaker trips to stop that wire from overheating.
What should the apprentice recommend?
The breaker is not the problem. It is the part telling you there is one.
A case · you decide
The 80% Rule and The Breaker size the charger
The 80% Rule & The Breaker — a 16-year-old apprentice helping plan a car-charger install
A customer wants to charge an electric car overnight on an existing 20 A, 120 V circuit. The charger can be set to draw 16 A or 20 A.
The 80% Rule: a continuous load (three hours or more) on a 20 A breaker may use only 16 A.
The Breaker still protects the wire. Running it at its limit all night is exactly what the rule prevents.
Which setting should they use?
The number is the safety. Continuous loads get a margin.